Alarm and Event
118 3BDS011222-510 B
2. Select the Group Alarm Manager aspect (refer to Figure 51).
Figure 51. Group Alarm Manager
Ensure that the Alarm Grouping Enabled and the Alarm Grouping On check
boxes are enabled. These settings are replicated from the System Configuration
Console. The Alarm Grouping On check box controls the behavior of the alarm
lists with configuration for alarm grouping set to Default. If Alarm Grouping
On is unchecked it is still possible to display the group alarms in an alarm list by
explicitly setting alarm grouping to On in the alarm list configuration. The Alarm
Grouping feature can also be enabled through the Group Alarm Manager
aspect.