Device Management FOUNDATION Fieldbus
3BDS011222-510 B 297
Load FF Devices
12. Select the H1 Link, a Linking Device or if sufficient only a single H1 device.
The complete HSE subnet can also be selected for commissioning. Previously
not reserved objects will not be considered for commissioning.
13. Open the Online dialog with Object > Online Dialog... (refer to Figure 177).
14. Wait until version check has completed, then switch to Download to device
tab.
The commissioning status in the tree structure indicates, which objects will be
loaded. Here, indicates that the object will not be loaded because on-line
data is up to date, indicates that an incremental download will be performed,
and indicates that a full download will be performed. and stand for
incremental or full download respectively where at an H1 link the Link Active
Scheduler (LAS) - the cyclic communication - will be stopped and at an H1
device the resource block will be stopped. indicates an element for which no
Figure 177. Online Dialog