Control Logic Section 2 Configuration
58 3BDS011222-510 B
Naming Conventions
To ensure that naming conventions are followed for diagrams, the property
DiagramSuffixString, available in Object Type Structure > Function Planning >
Settings > Function Settings aspect, can be used (refer to Figure 13). Set the
required suffix in the Value column. This suffix can be used as reference while
creating diagrams.
In the action display, the diagram reference name and its description is displayed in
the Signal column and the operation/action is displayed in Action column (refer to
Figure 14).
The Function Diagram containing the sequence with an output reference need to be
generated (using the Generate Configuration Data option) every time an input
reference with the same variable as this output reference is added. This ensures that
all the references are updated in SFC Viewer.
When the name of a target diagram that is being used in a sequence is changed,
the configuration data needs to be generated again for the this even though the
diagram status is shown as green.
Figure 14. Action Display with diagram reference name and its description