SMS and e-mail Messaging
212 3BDS011222-510 B
Alarm Manager Service Group Configuration
The Only send message if previous alarm condition was acknowledged in the
Alarm and Event Message Source is designed to prevent the same alarm condition
from sending several messages due to alarm chatter (alarm going from inactive to
active and back again several times over a relatively short period of time). However,
this option also requires configuration of the Alarm Manager Basic Service Group
in the Service Structure.
1. Use the Structure Selector to open the Service Structure in Plant Explorer.
2. Use the Object Browser to navigate to:
Services > Alarm Manager, Service > Basic Service, Service Group
3. Select Service Group Definition in the Aspect List Area.
4. Click the Special Configuration tab.
Figure 120. Service Group Definition Special Configuration Tab