Device Management PROFIBUS & HART
258 3BDS011222-510 B
Configuration of OPC Server PROFIBUS/HART
The OPC Server PROFIBUS/HART shall be configured only, if Asset Optimization
for asset monitoring is installed and used in System 800xA.
The OPC Server PROFIBUS/HART enables access to field device data without
requiring additional field wiring and provides these data to the Asset Optimization
Server.
Asset Monitors delivered with Device Types and installed via Device Library
Wizard are designed to read these device data from the OPC Server
PROFIBUS/HART and provide them to Asset Reporter and Asset Viewer.
Operators and maintenance personnel will be notified when an abnormal device
condition calls for maintenance action.
After completing the engineering work for HART and PROFIBUS devices in the
800xA system, the OPC Server PROFIBUS/HART can be configured to access field
device data for e.g. Asset Monitoring. Depending on the number of devices and its
device data accessed by the OPC Server special configurations might be required.
OPC Server Assignment to a Connectivity Server.
A Connectivity Server on which the OPC Server PROFIBUS/HART can be
executed is assigned to each Control Network.
1. Open 800xA Plant Explorers Workplace and switch to the Control Structure.
It is not allowed to use OPC server PROFIBUS/HART to acquire device data to
applications such as Trend, Graphics, Faceplates etc. Only Asset Optimization
server can be a client to PROFIBUS/HART OPC Server.
Only one OPC Server PROFIBUS/HART per Connectivity Server can be started.
OPC Servers of other software options, for example the AC 800M OPC Server,
can be executed on the same Connectivity Server.
This section describes the default configuration for the number of devices
released for the OPC Server PROFIBUS/HART. Please read System 800xA
Device Management, PROFIBUS and HART Configuration (3BDD011934*),
whether special configuration may be required to run the OPC Server properly.