CDA ci860 Specifications Page 244

  • Download
  • Add to my manuals
  • Print
  • Page
    / 604
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 243
Device Management PROFIBUS & HART
244 3BDS011222-510 B
Insert HART Device Type Objects
HART Device Type Objects are installed with the Device Library Wizard. Only the
device types Generic HART Transmitter and Generic HART Actuator are part
of the Device Integration Library - Basics system extension, which allows basic
configuration, operation and diagnosis of HART devices.
HART Device Types are available as standard Object Types in 800xA Plant
Explorers Object Type Structure. They are not based on Hardware Libraries and can
not be used in Control Builder M projects. Therefore HART Device Type Objects
can be exclusively used with Fieldbus Builder PROFIBUS/HART included in the
Device Management PROFIBUS & HART package. Insert of HART Device Types
Objects can be performed in the Plant Explorers Control Structure only.
HART Device Type Objects are integrated into the fieldbus topology as follows:
1. Open Plant Explorer.
2. Switch to Control Structure.
3. Open the substructure below the Project object.
To create or delete an instance of the HART device types with an Application
Engineer user role, either of following setting has to be done:
Change the security definition for Application Engineers to the
permissions Operate and Operator Configure.
Add the Operator role also to the Application Engineer role.
The Generic HART Device Objects are assigned to the Basic HART DTM using
HARTs universal and common practise commands. Only device specific HART
Type Objects installed via Device Library Wizard have the full capability of
configuration, operation, maintenance and diagnosis.
HART field devices are managed exclusively by the Fieldbus Builder
PROFIBUS/HART in the Control Structure of Plant Explorer and not be visible
in the Control Builder M project.
Cyclic data communication must have been started already by Control Builder M
Professional.
Field devices support the HART protocol can only be placed below I/O modules
that support this protocol in hardware and software (DTM) technology.