Alarm and Event
94 3BDS011222-510 B
Audible Alarms Toolbar
The Audible Alarms Toolbar must be included in the workplace toolbar (such as
the Application Bar) for the Audible Alarm function to work properly. Refer to
Figure 29.The operator clicks the icon to silence the audible alarms.
This is configured on the workplace object for the selected workplace. See System
800xA Operations, Operator Workplace Configuration (3BSE030322*) for more
information on how to include the Audible Alarms Toolbar in a workplace toolbar.
Configuration of Hot Key for silencing Audible Alarms
To configure a hot key for silencing audible alarms follow the steps below:
1. Go to the Workplace Structure and expand the Web System Workplace object.
2. Select your Workplace object and open the Hot Keys aspect.
3. Select hot key combination in the Hotkey text field. See Figure 30.
4. Select Execute Verb from the Action drop-down menu.
5. Browse to the Audible Alarm Workplace Configuration aspect in the Aspect
field.
6. Select the Silence Audible verb in the Verb field.
7. Click Add and the new hot key will be added in the list.
8. Click Apply.
Figure 29. Audible Alarms Toolbar