Device Management PROFIBUS & HART
3BDS011222-510 B 241
4. The sub menu of Device Functions... indicates the current mode (will be
Communication disabled for fieldbus configuration).
Insert S800 I/O Modules at AC 800M ModuleBus.
For instantiation of local S800 I/O modules to AC 800M Controller refer to Create
Hardware Units on page 38 and the following.
Insert PROFIBUS Communication Interface CI854(A).
The communication interface CI854(A) establishes the PROFIBUS network for an
AC 800M controller. Up to 12 CI854 can be placed at the Controller, 6 lines can be
build up in redundant mode. Also line redundancy is supported from each CI854
interface.
1. Open Plant Explorer.
2. Switch to Control Structure.
3. Open the substructure below the Project object.
The sub menu allows also changing the mode by selecting the menu item.
This subsection can be skipped, if no HART devices are used on local S800 I/O
modules.
The Hardware Library for CI854(A) has to be inserted and connected in the
Control Builder M project before performing the steps described below.
This section describes a simple PROFIBUS network configuration. Mainly the
configuration via Device Type Manager is part of this document.
Detailed information is provided in the relevant product documentation of
Control Builder M Professional. Additionally a document is also available
describing how to build up a physical PROFIBUS network.