Device Management PROFIBUS & HART
3BDS011222-510 B 235
In order that field devices can be accessed with DTM via the AC 800M controller,
the communication path (Tool Routing) must be enabled in each controller.
Tool Routing is disabled by default. In order to activate it, the processor module of
the AC 800M controller, e.g. PM860/TP860, is selected in Control Structure.
The Control Properties aspect appears in the aspect window. Select the aspect to
open an overview of the various properties of the module in the main Plant Explorer
window. One of the property entries is TOOLROUTING.
Figure 131. Control Structure with Fieldbus Topology
In 800xA system, communication with field devices through DTMs is possible,
only when Tool Routing is enabled.