Device Management PROFIBUS & HART
3BDS011222-510 B 237
Setting up a Fieldbus Topology for PROFIBUS and HART
The 800xA system is capable of setting up HART and PROFIBUS communication.
Together with the AC 800M Controller and local S800 modules HART devices can
be connected. Added with the CI854(A) communication interface (PROFIBUS) and
PROFIBUS remote I/O like ABB S800 or S900 a connection to HART devices can
be realized additionally.
PROFIBUS devices are connected directly to the CI854(A) communication
interface linked to the AC 800M controller or to PROFIBUS DP/PA Linking
Devices placed between CI854(A) and the PROFIBUS PA field device.
This section describes a sample set-up for local and remote S800 I/O modules with
HART Device Type Objects connected below as well as for PROFIBUS Devices
Type Objects.
The following steps have been performed in 800xA Plant Explorers Control
Structure, whereas S900/S800 I/O modules and PROFIBUS device types can also
be inserted in Control Builder M projects using Control Builder M Professional.
HART devices can be inserted in Plant Explorers Control Structure only.
Bulk Data Manager operations are supported for both the fieldbus protocols.
Do not copy paste communication DTM objects such as CI854, S800 Modules,
S900 modules. Instead create them manually or use Bulk Data Manager.
However, copy / paste of the device object type instances is supported.