CDA ci860 Specifications Page 396

  • Download
  • Add to my manuals
  • Print
  • Page
    / 604
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 395
PC, Network and Software Monitoring
396 3BDS011222-510 B
PC, Network and Software Monitoring
Workflow for creating and configuring IT Asset objects using PNSM Asset types.
This workflow is generic for any IT Asset type.
1. Create a new object of the appropriate IT Asset type in Control Structure, under
the IT OPC Server Network.
2. Edit the IT General Property aspect on the new object to set the appropriate
general asset configuration parameters.
3. If necessary, edit the individual IT Device aspects to set the device-specific
configuration parameters.
4. If necessary, add and configure additional IT Device aspects to the asset object.
This is done by:
a. Create a new aspect on the object of type IT Device.
b. On the configuration view of the new IT Device aspect, set the Current IT
Device Configuration setting to the appropriate Device Configuration.
c. Edit the device-specific parameters as appropriate.
5. Go to the IT Device Manager aspect, and press click Populate. To confirm that
the asset object was properly populated, view the property list on the IT
Control Connection aspect.
6. If you have Asset Optimization installed and a license for IT Asset Monitoring,
generate the Asset Monitor for the object. To do this: Click Generate on the IT
Device Manager aspect.
7. Go to Asset Optimization
a. Go to AO Server 1
b. Go to the Asset Optimization Server object
c. Go to the Asset Monitors Tab
d. Click on Load all AMs
For more details refer to System 800xA, PC, Network, and Software Monitoring
Configuration (3BUA000447*).