Alarm Analysis Configuration
3BDS011222-510 B 133
1. Add two or more Alarm Logger, Service Providers to a Service Group in the
Service Structure. See Figure 64.
2. Configure each Service Provider to run on the node where the printer is
connected. This is done from the Configuration tab on the Service Provider
Definition aspect.
3. Configure the printer attributes below the Special Configuration tab.
See Figure 63.
How to Create Parallel Redundancy for the Alarm Printers.
If you want to have parallel redundancy for the Alarm Printers then create two or
more Alarm Logger Service groups the Service Structure. The following example
also shows the possibility to have different layout for the Alarm Printers.
Follow the steps below to create a new configuration aspect for your logger function
layout:
1. Add a new Alarm Logger configuration in the Library Structure.
2. Go to the Service Structure to add service providers. You need to have:
one Service Group with one Service Provider for each printer.
3. In this example the default Logger Configuration aspect, delivered with the
system, can be used for one printer, and an own for the other, refer to Figure 65.