Device Management FOUNDATION Fieldbus
3BDS011222-510 B 301
Upload HSE Subnet
21. Exit Fieldbus Builder FF.
When the Fieldbus Builder FF configuration is being saved, the FF data are
automatically uploaded to the PPA. In the FF Management aspect of the HSE
Subnet object the status of the last upload is displayed by a traffic light. When
the upload failed, the Available Subnet Version and the Uploaded Version are
different.
22. If the upload failed select the FFUpload aspect and check the reason for the
upload failure in the aspect preview area.
23. After correction of the errors, an upload can be started manually by clicking
Upload.
After completion of the upload the Available Subnet Version and the Uploaded
Versi on are identical.
Step 5: Using FF Data
For use in the AC 800M
The FF signals entered in the HSEHostCI860 object in Fieldbus Builder FF are
automatically transferred to the CI860 object in Control Builder M.
The following steps require that the requisite hardware has been defined in a Control
Network in the Plant Explorer Control Structure.
1. Use the Structure Selector in the Plant Explorer Workplace to open the Control
Structure.
2. Navigate to the CI860 object in the Control Network.
3. Select Insert Object from the context menu.