Alarm Analysis Configuration
3BDS011222-510 B 137
3 unacknowledged, 5 active and 1 hidden alarm. Read more about Hiding on page
95. Refer to System 800xA Operations (3BSE036904*) for description of operation
of the Alarm Band.
Creating a Sequence Bar Aspect
The Sequence Bar provides an overview indication of the status of the Alarm List
selected for display. The number of alarms is set at configuration, and may be
between zero and ten.
The operator may select a band button to call the default aspect for the
associated
object. See Figure 68.
Create the Sequence Bar as described below:
1. Expand the Functional Structure, and select the Test object.
2. Create an Alarm Sequence Bar aspect and open the Config View.
3. Select the Alarm List aspect that is to be displayed in the Sequence Bar.
4. Enter a number from zero to ten in the Alarms to display text area.
5. Click Apply.