Control Logic Section 2 Configuration
56 3BDS011222-510 B
Editing Step Detail Diagram
You add action code in a step detail diagram, working similar as in a normal
Function Diagram.
A step has three outputs of data type Boolean:
N, P1, P0, to initiate Action, P1 Action, P0 Action.
P1 is true when the step becomes active, P0 is true when the step becomes inactive
and N is true while the step is active. In the simplest case the output N is connected
to a variable, diagram parameter or diagram reference. Diagram references can
either be connected to global or local variables. Global allows to connect to external
global variables. Local variables can be used to connect between
sequences/steps/diagram only.
Figure 12. Sequence Overview Diagram