Integrating OPC Servers into 800xA
3BDS011222-510 B 423
3. Perform an Upload. See Upload on page 439.
4. Check the Data Access functionality by looking in the Property View in the
Control Connection Aspect. See Configuring DA Connectivity on page 430.
How to Connect to an OPC DA Server in a Non-System Node
1. In Control Structure, create a new object of the type Generic OPC Server
Network and name it for example Generic OPC Net.
2. Follow the wizard to select Connectivity Server. See Figure 256. A Service
Group with the name SG_Generic OPC Net will be created and a Data Source
Definition Aspect will be configured with this Service Group.
Figure 255. Connection of an OPC Server in Control Structure
In most cases DCOM security settings need to be configured. For more
information see DCOM Security Settings for OPC on page 457.