Electronic Signature
398 3BDS011222-510 B
3. Set the password for the inactivity user in the Password field.
4. Set the time-out for automatic revert to inactivity user in the Revert to
Inactivity User drop-down menu.
5. Click Apply.
For further details refer to System 800xA, Administration and Security
(3BSE037410*).
Electronic Signature
Before activate the first and second signatures, set the Signature Required property
of System Settings aspect as True. System Setting aspect is placed in Admin
Structure under Administrative Objects\Domains\<node> system. Further configure
the First Signature required / Second Signature required on the Aspect Category
Definition aspect of the Aspect Category object in the Aspect System Structure. You
can choose to require First Signature or (First and) Second Signature. This is also
the place where to configure the required permission for signing via the Permissions
tab.
For further details refer to System 800xA, Administration and Security
(3BSE037410*).
Configuration Change Management
System Configuration Version
A System Configuration Version is defined by an System Configuration Version
Definition object /aspect in the Maintenance Structure beneath the System
Configuration Version Definitions root object. A version identity and a label can be
set in the Summary tab on the Backup Definition aspect of the System
Configuration Version Definition object. Backup / Creation of the System
Configuration Version can be started from this tab.
A System Configuration Version is stored in a corresponding object beneath the
System Configuration Versions root object.The corresponding backup files are
stored on a backup directory on harddisk.